Systematic AC & refrigeration system troubleshooting
⚠️
ELECTRICAL SAFETY - Always disconnect power before servicing. High voltage and capacitors can cause serious injury or death. Use proper PPE and lockout/tagout procedures.
Common Refrigerants:
0% Complete
🔌
Phase 1: Basic Power & Thermostat Verification
Verify thermostat calling for cooling
Set temp below room temp, mode on COOL, fan to AUTO, check display working
Check thermostat batteries (if applicable)
Replace batteries, wait for reboot, verify proper display and settings retained
Verify power at indoor unit
Check breaker ON, disconnect switch ON, measure 120VAC or 240VAC at unit
Verify power at outdoor unit
Check breaker ON, disconnect switch ON, measure 240VAC at unit
Verify drain clear, float switch not tripped, condensate pump working (if equipped)
❄️ IF EVAPORATOR COIL IS FROZEN
STOP: System must be thawed before continuing diagnostics Thaw procedure: Turn off cooling, run fan only for 1-3 hours, or use defrost mode if available Causes: Low airflow (dirty filter/coil), low refrigerant, metering device issue, blower failure
🌡️
Phase 3: Outdoor Unit Operation
Verify outdoor fan motor running
Check for 240VAC at motor, verify proper rotation direction (upward airflow)
Check condenser coil cleanliness
Dirty coil causes high head pressure - clean with coil cleaner and water
Verify compressor operation
Should run when calling for cool - listen for hum, feel for vibration, check amp draw
Check contactor operation
Verify 24VAC at coil, contacts pull in, 240VAC passes through to compressor/fan
Test run capacitor
Discharge safely, measure µF with meter - should be ±6% of rated value
Good: Within 6% of rating | Weak: 7-20% off | Failed: >20% off or shorted/open
Measure compressor amp draw
Compare to nameplate RLA (Rated Load Amps) and LRA (Locked Rotor Amps)
Verify 24" clearance all sides, no debris in unit, vegetation trimmed back
⚡ COMPRESSOR WON'T START
Hums but doesn't start: Bad capacitor, low voltage, mechanical seizure No sound/no amp draw: No power, bad contactor, internal overload tripped Clicking on/off: Overload cycling due to low voltage, bad cap, or compressor issue Hard start kit: May help marginal compressor start in heat - not a permanent fix
❄️
Phase 4: Refrigerant Charge & System Diagnostics
Connect manifold gauges to service ports
Blue hose to suction (large line), red hose to liquid (small line), yellow to vacuum pump/tank
Record ambient outdoor temperature
Required for proper pressure/charge analysis - measure in shade near unit
Measure suction pressure (low side)
With system running 10+ minutes - compare to P-T chart for refrigerant type
R-410A typical: 115-135 PSI @ 75°F indoor
Measure discharge pressure (high side)
Should correlate with outdoor ambient temp - check P-T chart
R-410A typical: 250-300 PSI @ 30°C (86°F) outdoor
Measure suction line temperature
Use temp clamp or probe at service port on large line
Calculate superheat
Superheat = Suction line temp - Saturated temp (from P-T chart at suction pressure)
Look for burned wires, loose terminals, corrosion - tighten all connections
Test high/low pressure switches (if equipped)
Verify switches closed during normal operation - open on fault condition
💡 CAPACITOR TESTING
ALWAYS discharge: Use insulated screwdriver across terminals before handling Visual inspection: Bulging top, oil leakage, burn marks = replace immediately Testing: Must use capacitance meter (not multimeter ohms setting) Replacement: Match or slightly higher µF rating OK, voltage must be equal or higher
🔬
Phase 6: Advanced System Analysis
Check metering device operation
TXV: Should adjust to load | Fixed orifice: Check for restrictions or ice
Measure airflow (if possible)
Target: 400 CFM per ton of cooling (e.g., 3-ton = 1200 CFM)
Use anemometer, flow hood, or temp rise method
Calculate system capacity
Use temp split and airflow: BTU/hr = 1.08 × CFM × ΔT
Check for non-condensables in system
High head pressure with low ambient = air in system (requires reclaim/recharge)
Test reversing valve (heat pump only)
Switch between heat and cool modes - feel lines shift hot/cold
Low oil or acid contamination indicates system failure
Document all measurements for report
Record pressures, temps, voltages, amps, superheat, subcooling, ambient conditions
🛠️ COMMON AC FAILURE MODES
Low refrigerant: High superheat, low subcooling, reduced capacity Dirty coils: High head pressure, high amps, reduced capacity Bad TXV: Erratic pressures, hunting, icing, or starved evaporator Compressor failure: No pressure rise, low amps, short cycling Restricted filter drier: High superheat, frost on drier, pressure drop across drier Low airflow: Icing, high superheat, reduced capacity, high suction temp