← Back to All Guides
❄️

Refrigeration System Diagnostics

Complete refrigeration cycle analysis and charge verification

💡
REFRIGERATION FUNDAMENTALS: Superheat and subcooling are the two most important measurements for diagnosing refrigerant charge and system performance. Master these calculations and you can diagnose 90% of refrigeration issues.
Select Refrigerant Type:
🧮 Superheat & Subcooling Calculator

Superheat Calculation

Suction Pressure (PSI)
Suction Line Temperature (°F)

Subcooling Calculation

Liquid Pressure (PSI)
Liquid Line Temperature (°F)
0% Complete
🛡️

Phase 1: Setup & Safety Procedures

⚠️ REFRIGERANT SAFETY
Never vent refrigerants: Illegal per EPA regulations, harmful to environment
Frostbite hazard: Liquid refrigerant at -40°F can cause instant frostbite
Asphyxiation risk: Refrigerants heavier than air, can displace oxygen in confined spaces
High pressure: R-410A can exceed 600 PSI - use proper equipment
📊

Phase 2: Pressure & Temperature Readings

📊 P-T Chart Reference (R-410A)
35°F Evap Temp
102 PSI
40°F Evap Temp
118 PSI
45°F Evap Temp
133 PSI
80°F Cond Temp
225 PSI
95°F Cond Temp
316 PSI
105°F Cond Temp
372 PSI
🌡️

Phase 3: Superheat Measurement & Analysis

🔍 SUPERHEAT DIAGNOSIS
Normal Superheat (8-12°F TXV): System charge is correct, metering device working properly
High Superheat (>15°F): Starved evaporator - low refrigerant charge, restricted metering device, restricted filter drier, or TXV stuck closed
Low Superheat (<5°F): Flooded evaporator - TXV stuck open, overcharge (rare), or low airflow causing low evap temp
Hunting Superheat (fluctuating): TXV cycling, low charge, moisture in system, or improper TXV bulb placement
🌊

Phase 4: Subcooling Measurement & Analysis

🔍 SUBCOOLING DIAGNOSIS
Normal Subcooling (8-15°F): System charge is correct, condenser performing properly
Low Subcooling (<5°F): Low refrigerant charge, liquid line restriction, or non-condensables in system
High Subcooling (>18°F): Overcharge, restricted airflow on condenser, restricted metering device, or TXV stuck closed
Zero Subcooling: Critically low charge - flashing in liquid line, severe capacity loss, compressor damage risk
🎯

Phase 5: Combined Superheat/Subcooling Analysis

🎯 COMBINED DIAGNOSIS MATRIX
High SH + Low SC: LOW REFRIGERANT CHARGE (most common) - add charge slowly
Low SH + High SC: OVERCHARGE or LOW AIRFLOW - check filter/coils before removing charge
High SH + High SC: RESTRICTED METERING DEVICE or filter drier - feel for temp drop
Low SH + Low SC: TXV STUCK OPEN or overcharge (rare) - check TXV operation
Normal SH + Normal SC: SYSTEM CHARGED CORRECTLY - look elsewhere for problem
🔍

Phase 6: Leak Detection Procedures

💡 LEAK DETECTION TIPS
Most common leak points: Service ports (40%), flare connections (30%), coil leaks (20%), brazed joints (10%)
UV dye: Inject on first visit if leak suspected, return in 1-2 weeks to find leak with UV light
Standing pressure: System with leak will lose pressure over days/weeks when off
Nitrogen test: For slow leaks, pressurize with nitrogen to 150-300 PSI and recheck
⚗️

Phase 7: Refrigerant Charging Procedures

⚠️ CHARGING SAFETY & BEST PRACTICES
Never liquid to suction: Will slug compressor and cause catastrophic damage
Charge slowly: Overcharging is worse than undercharging - go slow
Let system stabilize: Takes 5-10 min for accurate readings after adding charge
R-410A charging: Can be liquid or vapor (near-azeotropic blend) but vapor safer
Blended refrigerants: Must be removed and charged as liquid (R-407C, R-404A)

Phase 8: Final System Verification