Professional Training for HVAC Technicians, Students, and Educators
HVAC technicians, apprentices, students, educators
6-8 hours (including assessments)
Digital Certificate of Completion
CSA B52, B149.1-25, TSSA Standards
Understanding the basics of mildly flammable refrigerants
The HVAC industry is undergoing a major shift as we transition from high-GWP HFC refrigerants to lower-GWP alternatives. A2L refrigerants—such as R-32 and R-454B—are now being widely adopted in Canada due to their lower environmental impact.
Classification | Toxicity Level | Flammability Characteristics | Common Examples | Canadian Safety Level | CSA B52-22 Requirements |
---|---|---|---|---|---|
A1 | Lower (OEL ≥400 ppm) | No Flame Propagation | R-134a, R-410A, R-404A | Highest | Standard protocols |
A2L | Lower (OEL ≥400 ppm) | Lower Flammability (<3.9 in/s) | R-32, R-454B, R-1234yf, R-452B | High with precautions | Enhanced detection & ventilation required |
A2 | Lower (OEL ≥400 ppm) | Higher Flammability | R-152a, R-290 (Propane) | Moderate | Special handling & detection required |
A3 | Lower (OEL ≥400 ppm) | Highest Flammability | R-600a (Isobutane), R-170 | Lowest | Extreme caution protocols |
B1, B2L, B2, B3 | Higher (<400 ppm) | Various Flammability | R-123, Ammonia variants | Restricted | Special training & equipment required |
All A2L refrigerant work in Canada must comply with:
Used in mini-splits, VRF, and packaged equipment. GWP of 675 (much lower than R-410A's 2088).
Replaces R-410A in many new units. Designed as a lower-GWP alternative.
R-1234yf, R-1234ze (less common in Canada, but growing).
A2Ls are not "drop-in" replacements. They require new equipment, updated codes, and special handling procedures.
Correct! R-32 is classified as an A2L refrigerant - lower toxicity and mildly flammable.
Understanding Canadian codes and standards for A2L refrigerants
Now includes A2L-specific provisions for charge limits, ventilation, and leak detection. This is your primary reference for A2L installations.
Covers piping, venting, and appliance requirements for A2L systems when integrated with gas heating systems.
Enforces compliance in Ontario, issues bulletins and inspection protocols for A2L installations.
Always check the latest code updates and TSSA advisories before starting any A2L project. Codes are updated regularly!
Correct! CSA B52 Sections 6 & 7 cover piping and ventilation requirements, and you must always follow the manufacturer's installation manual.
Understanding the physical and chemical characteristics
Refrigerant | LFL (% vol) | UFL (% vol) | Burning Velocity (in/s) | Ignition Energy (mJ) | CSA B52-22 Classification |
---|---|---|---|---|---|
R-32 | 14.4 | 29.3 | 2.6 | 15-20 | A2L |
R-454B | 15.2 | 28.7 | 2.3 | 18-25 | A2L |
R-1234yf | 6.2 | 12.3 | 1.5 | 3-5 | A2L |
R-452B | 16.1 | 30.2 | 2.8 | 12-18 | A2L |
Property | R-32 | R-454B | R-1234yf | R-452B | Units |
---|---|---|---|---|---|
Molecular Weight | 52.02 | 69.5 | 114.04 | 69.4 | g/mol |
Boiling Point | -51.7 | -47.1 | -29.5 | -49.8 | °C |
Critical Temperature | 78.1 | 95.7 | 94.7 | 82.4 | °C |
Critical Pressure | 57.8 | 46.1 | 33.8 | 45.5 | bar |
GWP (AR5) | 675 | 466 | 4 | 698 | - |
ODP | 0 | 0 | 0 | 0 | - |
Safety Classification | A2L | A2L | A2L | A2L | ASHRAE 34 |
Correct! False. A2L refrigerants require special storage considerations due to their mild flammability.
Click on the correct storage area for A2L cylinders in this diagram:
Design requirements and installation best practices
CSA B52 Table 5 specifies maximum refrigerant charges based on room volume and occupancy:
Maximum Charge = Room Volume (m³) × 0.307 kg/m³
For occupied spaces without additional safety measures
Exceeding these limits requires:
✅ Approved:
❌ Not Permitted:
Mandatory in certain occupancy types:
Correct! Soldered joints are not permitted for A2L refrigerants due to their lower melting point and potential for failure.
Personal protective equipment and safety procedures
Correct! Always shut down ignition sources first and increase ventilation to prevent accumulation of flammable vapors.
Match the PPE item to the hazard it addresses:
Safe service procedures and maintenance practices
Only use recovery machines specifically rated for A2L refrigerants!
Standard recovery machines are not safe for mildly flammable refrigerants and may create ignition hazards.
Correct! A2L-rated recovery equipment is mandatory for safety reasons and code compliance.
Apply knowledge to practical field situations
Situation: A customer's rooftop R-454B unit is tripping on high pressure. Upon arrival, you notice a faint refrigerant odor near the unit.
Unit Details:
Examine this installation photo and identify all code violations:
Correct! Safety is always the first priority. Don PPE and ensure the area is safe before beginning any diagnostic work.
Violations identified: Missing A2L label, soldered connections, improper cylinder storage, and inadequate ventilation are all serious code violations.
Demonstrate your A2L refrigerant safety knowledge
Make sure you've completed all previous modules before starting.